Company Information | ||||||||
[email protected] | ||||||||
Mobile | +8613666084105 | |||||||
+8613666084105 | ||||||||
13666084105 | ||||||||
Add | Room 1004, No. 62 Xiangxiu Li, Siming District, Xiamen City, Fujian Province, China |
Product Introduction
The Honeywell MU-TAIH52 is a high-level analog input (HLAI) module designed for use in Honeywell’s Experion Process Knowledge System (PKS) and Experion LX systems. It features 16 analog input channels and supports Smart Transmitter Interface (STI) redundancy, ensuring reliable data acquisition in critical industrial applications. This module is suitable for hazardous environments, complying with Class 1, Division 2 standards.
Product Specifications
Parameter | Details |
Model Number | MU-TAIH52 |
Part Number | 51304337-200 |
Input Channels | 16 |
Input Type | High-Level Analog Input (HLAI) |
Protocol | Honeywell DE (bidirectional) |
Maximum Input Voltage | -10V to +30V (no damage) |
Resolution | Matches connected field instrument |
Accuracy | Maintains accuracy of connected instrument without degradation |
Transmitter Broadcast Rate | 2.4–3.6 PVs/sec per channel (configuration-dependent) |
Current Limiting | 145 Ω resistor (not fused) |
Power Supply Voltage | Minimum 23V |
Maximum Current | 30 mA |
Terminal Type | Screw terminals |
Dimensions | 137 x 51 x 151 mm |
Operating Environment | Class 1, Division 2 hazardous locations |
Weight | 0.5 kg |
Product Applications
-
Process Control Systems: Integration with Honeywell Experion PKS and LX systems for precise analog signal acquisition.
-
Industrial Automation: Monitoring and control of various industrial processes requiring high-level analog inputs.
-
Hazardous Environments: Suitable for use in Class 1, Division 2 areas, such as chemical plants and oil refineries.
-
Smart Transmitter Integration: Supports Honeywell DE protocol for bidirectional communication with smart field devices.
Product Advantages
-
High Channel Density: Provides 16 analog input channels in a compact module, optimizing cabinet space.
-
Enhanced Reliability: STI redundancy ensures continuous operation and data integrity in critical applications.
-
Protocol Support: Compatible with Honeywell DE protocol, facilitating seamless integration with smart transmitters.
-
Robust Design: Engineered to operate reliably in hazardous environments, complying with industry safety standards.
Frequently Asked Questions (FAQ)
-
What is the primary function of the MU-TAIH52 module?
-
It serves as a high-level analog input module, acquiring analog signals from field devices and transmitting them to the control system.
-
-
How many input channels does the module support?
-
The module supports 16 analog input channels.
-
-
Is the MU-TAIH52 compatible with smart transmitters?
-
Yes, it supports Honeywell DE protocol for bidirectional communication with smart field devices.
-
-
What is the maximum input voltage the module can handle?
-
It can handle input voltages ranging from -10V to +30V without damage.
-
-
Does the module provide input isolation?
-
Yes, all inputs are isolated from ground and each other, enhancing signal integrity and safety.
-
-
What is the module’s operating environment classification?
-
It is suitable for Class 1, Division 2 hazardous locations.
-
-
What are the physical dimensions of the module?
-
The module is classified as Size B, 137 x 51 x 151 mm.
-
-
What is the weight of the MU-TAIH52 module?
-
It weighs 0.5 kg.
-
-
What type of terminals does the module use?
-
It utilizes screw terminals for secure and reliable connections.
-
-
Can the module be used in redundant configurations?
-
Yes, it supports STI redundancy, allowing for high-availability system designs.
-
Related Models from the Same Series
Model Number | Description | Function |
MU-TAIH02 | High Input Analog / STI Input Terminal Assembly | 16-channel analog input module with STI support |
MU-GAIH12 | High-Level Analog Input FTA | 12-channel analog input module |
MU-GAIH82 | High-Level Analog Input FTA | 8-channel analog input module |
MU-TAMR03 | Analog Multiplexer Redundant Module | Provides multiplexing for analog signals |
MU-TDPR02 | Digital Input Redundant Module | Handles digital input signals with redundancy |
MU-TLPA02 | Low Power Analog Input Module | Designed for low-power analog signal acquisition |
Popular Honeywell Models
Model Number | Description | Function |
CC-PAIH01 | Analog Input Module | 16-channel analog input module for C300 controller |
CC-PDIL01 | Digital Input Module | 32-channel digital input module for C300 controller |
CC-PAOH01 | Analog Output Module | 8-channel analog output module for C300 controller |
CC-PDOB01 | Digital Output Module | 32-channel digital output module for C300 controller |
CC-TDIL01 | Digital Input Module | 16-channel digital input module for C200 controller |
CC-TAOX01 | Analog Output Module | 8-channel analog output module for C200 controller |